- bounce time typ:
- 3.5 ms
- color:
- Gray
- connection technology:
- CAGE CLAMP
- contact material relay:
- AgNi + Au
- country of origin sales organisation germany:
- DE
- depth from upper edge of din rail:
- 56 mm / 2.205 inch
- dielectric strength control load circuit ac 1 min:
- 4 kVrms
- dielectric strength open contact ac 1 min:
- 1 kVrms
- drop out time typ:
- 6 ms
- electrical life no resistive load 23 c:
- 50 x 103 switching operations
- fine stranded conductor:
- 0.08 2.5 mm / 28 14 AWG
- fire load:
- 0.313 MJ
- height:
- 91 mm / 3.583 inch
- input voltage range:
- -30 +25 %
- limiting continuous current:
- 0.208333333333333
- mechanical life:
- 5 x 106 switching operations
- mounting type:
- DIN-35 rail
- nominal input current at un:
- 10 mA
- nominal input voltage un:
- DC 24 V
- note:
- To prevent damaging the gold layer, 30 V switching voltages and 50 mA currents must not be exceeded. Higher switching power eventually evaporates the gold layer. The resulting deposits in the housing may reduce service life.To protect the relay coils
- number of changeover switchover contacts:
- 1
- operating altitude max:
- 2000 m
- packaging type:
- Box
- pollution degree:
- 2
- processing temperature:
- -25 +50 C
- pull in time typ:
- 6 ms
- rated surge voltage:
- 4 kV
- rated voltage:
- 250 V
- recommended minimum load:
- 1 V / 1 mA / 1 mW
- relative humidity:
- 5 95 % (no condensation permissible)
- solid conductor:
- 0.08 2.5 mm / 28 14 AWG
- standards specifications:
- EN 61010-2-201 || EN 61810-1 || EN 61373 || GL || UL 508
- status indicator:
- Red LED
- strip length:
- 5 6 mm / 0.2 0.24 inch
- surrounding air temperature operation at un:
- -40 70 C
- surrounding air temperature storage:
- -40 70 C
- switching frequency with without load max:
- 6 min-1 / 180 min-1
- switching power resistive max:
- AC 1250 VA: DC (see load limit curve)
- switching voltage max:
- AC 250 V
- weight:
- 22.099 g
- width:
- 6 mm / 0.236 inch