- For type K, S, B and R thermocouples
- Cold junction compensation (on/off)
- Switching between measurement ranges is calibrated
- Detect sensor's wire break
- Detection: measurement range underflow/measurement range overflow
- Clipping function limits the analog standard signal to the upper range values
- Safe 3-way isolation with 2.5 kV test voltage per EN 61140
The WAGO 857 series temperature signal conditioner features a DIP switch, one analog input for thermocouples (types K, S, B, R), and one analog output with multiple configurations (0-10mA, 2-10mA, 0-20mA, 4-20mA, 0-5Vdc, 1-5Vdc, 0-10Vdc, 2-10Vdc). It operates on a supply voltage of 16.8-26.4Vdc (24Vdc nominal) and includes Push-in CAGE CLAMP spring connections for easy installation on a DIN-35 rail (6mm width). The device is rated for an ambient temperature range of -25°C to +70°C and has an IP20 protection rating, equivalent to model 857812.
- cold junction compensation:
- ON/OFF (default: ON)
- cold junction error:
- 3 K (typ. 2 K )
- configuration options:
- DIP switch
- conformity marking:
- CE
- connection technology:
- Push-in CAGE CLAMP
- country of origin sales organisation germany:
- DE
- depth from upper edge of din rail:
- 97.8 mm / 3.85 inch
- emc emission of interference:
- EN 61000-6-4
- emc immunity to interference:
- EN 61000-6-2
- fine stranded conductor:
- 0.34 2.5 mm / 22 14 AWG
- fire load:
- 0.000 MJ
- height:
- 94 mm / 3.701 inch
- input signal type:
- TC sensors
- load impedance current output:
- ¤ 600
- load impedance voltage output:
- 2 k
- mounting type:
- DIN-35 rail
- nominal supply voltage us:
- DC 24 V
- operating altitude max:
- 2000 m
- output signal current:
- 0 10 mA: 2 10 mA: 0 20 mA: 4 20 mA
- output signal type:
- Current || Voltage
- output signal voltage:
- 0 5 V: 1 5 V: 0 10 V: 2 10 V
- packaging type:
- Bag
- power consumption at nominal supply voltage:
- ¤ 40 mA
- power supply type:
- 24 VDC
- relative humidity:
- 5 95 % (no condensation permissible)
- sensor types tc:
- Type K || Type S || Type B || Type R
- solid conductor:
- 0.08 2.5 mm / 28 14 AWG
- step response typ:
- 60 ms (Cold junction compensation (Off)): 120 ms (Cold junction compensation (ON))
- strip length:
- 9 10 mm / 0.35 0.39 inch
- supply voltage range:
- 30 %
- surrounding air temperature operation:
- -25 70 C
- surrounding air temperature storage:
- -40 85 C
- temperature coefficient:
- ¤ 0.04 %/K
- temperature measurement range tc:
- 0 1200 C (Type K): 0 1600 C (Type S): 600 1800 C (Type B): 0 1600 C (Type R)
- test voltage input output supply:
- AC 2.5 kV: 50 Hz: 1 min
- transmission error for the set measurement range:
- ¤ (150 K/set measurement range [K]) %
- transmission error typ:
- ¤ 0.1 % at full measurement span
- weight:
- 35.700 g
- width:
- 6 mm / 0.236 inch