- conformity marking:
- CE
- connection technology:
- Push-in CAGE CLAMP
- connection type 1:
- Input/output
- control deviation:
- ¤ 1 %
- country of origin sales organisation germany:
- CN
- default setting:
- DC 24 V
- depth:
- 56 mm / 2.205 inch
- depth from upper edge of din rail:
- 52.5 mm / 2.067 inch
- derating:
- -2.66 %/K (> 55 C)
- deviation dynamic load change 10 90:
- ¤ 1 %
- discharge current:
- ¤ 0.25 mA
- efficiency typ:
- 90 % (230 VAC): 89 % (110 VAC)
- fine stranded conductor:
- 0.2 2.5 mm / 24 12 AWG
- fire load:
- 0.117 MJ
- flammability class per ul94:
- V0
- height:
- 90 mm / 3.543 inch
- input current ii:
- ¤ 3.8 A
- input voltage derating:
- -2 %/V (< 100 VAC)
- input voltage range:
- AC 90 132 V: AC 180 264 V: DC 250 375 V
- inrush current:
- ¤ 20 A
- internal fuse:
- T 3.15 A / 500 VAC
- isolation voltage pri sec:
- DC 4.242 kV
- mains failure hold up time:
- 30 ms
- mounting type:
- DIN-35 rail || Screw mount (back)
- mtbf:
- > 500,000 h (per IEC 61709)
- nominal input voltage ui nom:
- 1 x AC 100 120 V: AC 200 240 V
- nominal mains frequency range:
- 47 63 Hz: 0 Hz
- nominal output current io nom:
- 6 A: 4.8 A (< 110 VAC)
- nominal output power:
- 150 W
- nominal output voltage uo nom:
- DC 24 V (SELV)
- note dimensions:
- Depth: 48 mm (without cover)
- open circuit proof:
- Yes
- operation status indicator:
- Green LED (Uo)
- output voltage range:
- DC 22 26 V (adjustable)
- overload behavior:
- Constant power (in overload range: 1.05 1.35 x Io nom): Shutdown and automatic restart in the event of a short circuit or permanent overload
- overvoltage protection secondary:
- ¤ 31 VDC (in the event of a fault)
- packaging type:
- Box
- parallel operation:
- Yes
- phases:
- 1
- pollution degree:
- 2
- power factor:
- 0.5
- power factor correction pfc:
- Passive
- power loss max pl max:
- 16.5 W (100 VAC / 24 VDC: 6 A)
- power loss pl:
- ¤ 0.4 W (230 VAC: No load)
- protection class:
- I
- protection type:
- IP20 (per EN 60529)
- recommended backup fusing:
- Circuit breaker: 6 A (C characteristic), 10 A (B characteristic) or higher
- relative humidity:
- ¤ 95% (no condensation permissible)
- required backup fusing:
- An external DC fuse is required for the DC input voltage.
- residual ripple:
- ¤ 100 mV (Peak-to-peak)
- resistance to reverse feed:
- ¤ DC 35 V
- series operation:
- Yes
- short circuit protected:
- Yes
- signaling:
- 1 x LED DC OK (green)
- solid conductor:
- 0.2 2.5 mm / 24 12 AWG
- standards specifications:
- EN 61204-3 || EN 60335-1 || EN 62368-1 || UL 60950-1 || UL 508
- strip length:
- 9 10 mm / 0.35 0.39 inch
- surrounding air temperature operation:
- -25 70 C
- surrounding air temperature storage:
- -40 85 C
- transient suppression primary:
- Varistor
- wago connector:
- picoMAX 5.0, WAGO 2092 Series
- weight:
- 510.000 g
- width:
- 144 mm / 5.669 inch