Schneider Electric SR2B121FU compact smart relay, Zelio Logic SR2 SR3, 12 IO, 100 to 240V AC, clock, display
Schneider Electric
$288.00
This Zelio Logic SR2 compact smart relay / programmable controller uses a supply voltage of 100V to 240V alternating current. It has 12 inputs / outputs with screw-clamp terminals, has an integrated clock and LCD display. It has compact design, allowing installation on DIN rail. It also offers simple programming, display and diagnosing of malfunctions display and navigation buttons. Its simple ladder programming makes it adapted for non-specialists.
- Clock:
- with
- Range Of Product:
- Zelio Logic
- Protection Type:
- against inversion of terminals (control instructions not executed)
- Cycle Time:
- 6-90 ms
- Analogue Input Number:
- 0
- Isolation Voltage:
- 1780 V
- Operating Altitude:
- 6561.68 ft (2000 m)
- Tightening Torque:
- 0.5 N.m
- Relative Humidity:
- 95-95 % without condensation or dripping water
- Overvoltage Category:
- III IEC 60664-1
- Current State 1 Guaranteed:
- >= 0.17 mA discrete input)
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Maximum Altitude Transport:
- 3048 m
- Voltage State 1 Guaranteed:
- >= 79 V discrete input
- Product Certifications:
- GL || GOST || UL || CSA || C-tick
- Environmental Disclosure:
- ENVPEP060406EN
- [Uimp] Rated Impulse Withstand Voltage:
- 4 kV EN/IEC 60947-1 and EN/IEC 60664-1
- Disturbance Radiated/Conducted:
- class B EN 55022-11 group 1
- China Rohs Regulation:
- X
- Number Of Outputs:
- 4 relay
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weight:
- 0.25 kg
- Power Consumption In Va:
- 7 VA without extension
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Current State 0 Guaranteed:
- <= 0.5 mA discrete input)
- Rohs Exemption Information:
- Yes
- Discrete Input Current:
- 0.6 mA
- Switching Capacity In Ma:
- >= 10 mA 12 V relay output)
- Voltage State 0 Guaranteed:
- <= 40 V discrete input
- Environmental Characteristic:
- EMC directive IEC 61000-6-2 || EMC directive IEC 61000-6-3 || EMC directive IEC 61000-6-4 || EMC directive IEC 61131-2 zone B || low voltage directive IEC 61131-2
- Electrical Durability:
- AC-12 500000 cycles 230 V, 1.5 A relay output IEC 60947-5-1 || AC-15 500000 cycles 230 V, 0.9 A relay output IEC 60947-5-1 || DC-12 500000 cycles 24 V, 1.5 A relay output IEC 60947-5-1 || DC-13 500000 cycles 24 V, 0.6 A relay output IEC 60947-5-1
- Warranty:
- 18 months
- Operating Rate In Hz:
- 0.1 Hz at Ie)relay output || 10 Hz no load)relay output
- Backup Time:
- 10 years 25°C
- Local Display:
- with
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Ambient Air Temperature For Storage:
- -40-70°C
- Supply Frequency:
- 50/60 Hz
- Mechanical Durability:
- 10000000 cycles relay output
- [Us] Rated Supply Voltage:
- 100...240 V AC
- Maximum Supply Current:
- 30 mA 240 V without extension) || 80 mA 100 V without extension)
- Mercury Free:
- Yes
- Response Time:
- 50 ms ladder from state 0 to state 1)discrete input || 50 ms ladder from state 1 to state 0)discrete input || 50...255 ms FBD from state 0 to state 1)discrete input || 50...255 ms FBD from state 1 to state 0)discrete input || 10 ms from state 0 to st
- Discrete Input Frequency:
- 47...53 Hz || 57...63 Hz
- Ambient Air Temperature For Operation:
- -20-40°C in non-ventilated enclosure IEC 60068-2-1 and IEC 60068-2-2 || -20-55°C IEC 60068-2-1 and IEC 60068-2-2
- Clock Drift:
- 12 min/year 0-55°C || 6 s/month 25-25°C
- Output Thermal Current:
- 8 A for all 4 outputs relay output
- Pvc Free:
- Yes
- Country of Origin:
- United States
- Ip Degree Of Protection:
- IP20 IEC 60529 terminal block) || IP40 IEC 60529 front panel)