- Pvc Free:
- Yes
- Pollution Degree:
- 3 IEC 60947-1
- Product Name:
- PowerPact L
- Suitability For Isolation:
- yes IEC 60947-2
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Ambient Air Temperature For Operation:
- -25-70°C
- Awg Gauge:
- AWG 2/0...500 kcmil aluminium/copper
- Tightening Torque:
- 50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
- Eu Rohs Directive:
- Compliant with Exemptions
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Device Application:
- distribution
- Ambient Air Temperature For Storage:
- -50-85°C
- Warranty:
- 18 months
- Country of Origin:
- United States
- Color:
- Black
- Circularity Profile:
- ENVEOLI2206029EN
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Control Type:
- toggle
- Depth:
- 110 mm
- Product Certifications:
- UL || CSA || NOM
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Environmental Disclosure:
- ENVPEP2206029EN
- Breaking Capacity Code:
- J
- Local Signaling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Mercury Free:
- Yes
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3 S, LSI
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Protection Technology:
- current limiter
- Range:
- PowerPact
- Trip Unit Name:
- MicroLogic 3.3 S
- Ip Degree Of Protection:
- front cover IP40
- Utilisation Category:
- category A
- Network Frequency:
- 50/60 Hz
- Terminal Identifier:
- AL600LS52K4
- Length:
- 31 mm
- Line Rated Current:
- 600-600 A
- Device Short Name:
- L-Frame
- Weight:
- 6.2 kg
- Communication Interface:
- Modbus || Ethernet
- Rohs Exemption Information:
- Yes
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Sustainable Offer Status:
- Green Premium product
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Poles Description:
- 4P