Contactor, TeSys K, 4P, 4 NO, AC-1, lt or eq to 440V 10A, 220 to 230VAC coil
- Irms Rated Making Capacity:
- 110 A AC for power circuit conforming to IEC 60947
- Rated Breaking Capacity:
- 110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
- Warranty:
- 18 months
- Device Application:
- control
- Heat Dissipation:
- 3-3 W
- Standards:
- EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- Poles Description:
- 4P
- Weight:
- 0.225 kg
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Operating Time:
- 30...40 ms coil energisation and NO closing || 30 ms coil de-energisation and NO opening
- Signaling Circuit Frequency:
- <= 400 Hz
- Associated Fuse Rating:
- 25 A gG at <= 440 V for power circuit || 25 A aM for power circuit
- Mechanical Durability:
- 10 Mcycles
- Average Impedance:
- 3 mOhm - Ith 20 A 50 Hz for power circuit
- Flame Retardance:
- V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
- Sustainable Offer Status:
- Green Premium product
- [Ith] Conventional Free Air Thermal Current:
- 20 A (at 60°C) for power circuit || 10 A (at 50°C) for Signaling circuit
- Range:
- TeSys
- [Ui] Rated Insulation Voltage:
- power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA C22.2 No 14
- Device Short Name:
- LC7K
- Product Certifications:
- CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
- Contactor Application:
- resistive load
- Country of Origin:
- France
- Control Circuit Type:
- AC 50/60 Hz silent
- Width:
- 45 mm
- Connections - Terminals:
- screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4
- Depth:
- 57 mm
- Maximum Operating Rate:
- 3600 cyc/h
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Tightening Torque:
- 0.8-1.3 N.m screw clamp terminals Philips No 2 || 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm || 0.8-1.3 N.m screw clamp terminals pozidriv No 2
- Rohs Exemption Information:
- Yes
- Eu Rohs Directive:
- Compliant with Exemptions
- Circularity Profile:
- ENVEOLI1503003EN
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- Utilisation Category:
- AC-1
- [Uc] Control Circuit Voltage:
- 220...230 V AC 50/60 Hz
- Ip Degree Of Protection:
- IP2X VDE 0106
- Ambient Air Temperature For Storage:
- -50-80°C
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Hold-In Power Consumption In Va:
- 3-3 VA (at 20°C)
- Mercury Free:
- Yes
- Product Or Component Type:
- contactor
- Control Circuit Voltage Limits:
- operational: 0.85...1.1 Uc (at <50°C) || drop-out: >= 0.10 Uc (at <50°C)
- Mechanical Robustness:
- shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on X axis6 Gn for 11
- Net Weight:
- 0.225 kg
- Protective Treatment:
- TC IEC 60068 || TC DIN 50016