- Control Circuit Voltage Limits:
- operational: 0.8...1.15 Uc (at <50°C) || drop-out: >= 0.20 Uc (at <50°C)
- Product Certifications:
- CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
- Rated Breaking Capacity:
- 110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
- Standards:
- EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ
- Pole Contact Composition:
- 4 NO
- Depth:
- 57 mm
- Net Weight:
- 0.18 kg
- Hold-In Power Consumption In Va:
- 4.5-4.5 VA (at 20°C)
- Overvoltage Category:
- III
- Operating Time:
- 10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing
- Rohs Exemption Information:
- Yes
- Product Or Component Type:
- contactor
- Mechanical Durability:
- 10 Mcycles
- Mechanical Robustness:
- shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on X axis6 Gn for 11
- Sustainable Packaging:
- Yes
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
- Irms Rated Making Capacity:
- 110 A AC for power circuit conforming to IEC 60947
- Associated Fuse Rating:
- 25 A gG at <= 440 V for power circuit || 25 A aM for power circuit
- Ip Degree Of Protection:
- IP2X VDE 0106
- Poles Description:
- 4P
- Mercury Free:
- Yes
- Device Application:
- control
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Control Circuit Type:
- AC 50/60 Hz
- Height:
- 58 mm
- Contactor Application:
- resistive load
- Average Impedance:
- 3 mOhm - Ith 20 A 50 Hz for power circuit
- Protective Treatment:
- TC IEC 60068 || TC DIN 50016
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Toxic Heavy Metal Free:
- Yes
- Maximum Operating Rate:
- 3600 cyc/h
- [Icw] Rated Short-Time Withstand Current:
- 90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 20 A 50°C - >= 15 min
- Connections - Terminals:
- screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4
- Heat Dissipation:
- 1.3-1.3 W
- Electrical Durability:
- 0.16 Mcycles 20 A AC-1 <= 690 V
- Mounting Support:
- rail || plate
- Weight:
- 0.18 kg
- Utilisation Category:
- AC-1
- Circularity Profile:
- ENVEOLI1503003EN
- Warranty:
- 18 months
- Range:
- TeSys
- [Uc] Control Circuit Voltage:
- 220...230 V AC 50/60 Hz
- Eu Rohs Directive:
- Compliant
- Sustainable Offer Status:
- Green Premium product
- [Ui] Rated Insulation Voltage:
- power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA C22.2 No 14
- Inrush Power In Va:
- 30-30 VA (at 20°C)
- Operating Altitude: