- Quality Labels:
- CE
- Ip Degree Of Protection:
- front cover IP40
- Device Application:
- distribution
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Length:
- 25 mm
- Width:
- 104 mm
- Trip Unit Technology:
- thermal-magnetic
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Range:
- PowerPact
- Ambient Air Temperature For Storage:
- -50-85°C
- Line Rated Current:
- 225-225 A
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Ambient Air Temperature For Operation:
- -25-70°C
- Weight:
- 2.4 kg
- Rohs Exemption Information:
- Yes
- Protection Type:
- overload protection || short-circuit protection
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Wire Stripping Length:
- 25 mm
- Pvc Free:
- Yes
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Terminal Identifier:
- AL250JD
- Mercury Free:
- Yes
- Height:
- 191 mm
- Environmental Disclosure:
- ENVPEP2206031EN
- Circuit Breaker Application:
- HACR rated
- Net Weight:
- 2.4 kg
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Communication Interface:
- Modbus || Ethernet
- Circularity Profile:
- ENVEOLI2206031EN
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Suitability For Isolation:
- yes IEC 60947-2
- Electrical Connection:
- lugs, line || lugs, load
- Mounting Support:
- lug
- Poles Description:
- 3P
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Local Signaling:
- switched off (OFF) 1 trip indicator green)
- Control Type:
- toggle
- Breaking Capacity Code:
- G
- Pollution Degree:
- 3 IEC 60947-1
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Eu Rohs Directive:
- Compliant with Exemptions
- Magnetic Tripping Current:
- 500-850 A
- Continuous Current Rating:
- 0.8
- Warranty:
- 18 months
- Product Certifications:
- UL || CSA || NOM
- Mounting Mode:
- unit mount lug)
- Product Or Component Type:
- circuit breaker