- Product Certifications:
- UL || CSA || NOM
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Mounting Support:
- lug
- Terminal Identifier:
- AL250JD
- Protection Type:
- overload protection || short-circuit protection
- Control Type:
- toggle
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Communication Interface:
- Modbus || Ethernet
- Magnetic Tripping Current:
- 2000-2000 A
- Mounting Mode:
- unit mount lug)
- Mercury Free:
- Yes
- Net Weight:
- 2.4 kg
- Depth:
- 86 mm
- Sustainable Offer Status:
- Green Premium product
- Length:
- 25 mm
- Suitability For Isolation:
- yes IEC 60947-2
- Country of Origin:
- United States
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Pollution Degree:
- 3 IEC 60947-1
- Range:
- PowerPact
- Environmental Disclosure:
- ENVPEP2206031EN
- Warranty:
- 18 months
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Weight:
- 2.4 kg
- Rohs Exemption Information:
- Yes
- Electrical Connection:
- lugs, line || lugs, load
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Product Name:
- PowerPact J
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Device Application:
- distribution
- Wire Stripping Length:
- 25 mm
- Eu Rohs Directive:
- Compliant with Exemptions
- Ambient Air Temperature For Operation:
- -25-70°C
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Local Signaling:
- switched off (OFF) 1 trip indicator green)
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Network Frequency:
- 50/60 Hz
- Breaking Capacity Code:
- G
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Utilisation Category:
- category A
- Pvc Free:
- Yes
- Trip Unit Technology:
- thermal-magnetic
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Continuous Current Rating:
- 0.8
- Ip Degree Of Protection:
- front cover IP40