Schneider Electric DPE50BD IEC contactor,Easy TeSys DPE,nonreversing,50A,3P,30HP at 480V AC,24VDC coil
Schneider Electric
$109.00
Easy TeSys DPE IEC contactor, 3 poles (3NO), for motor control applications up to 50A/690V AC-3 (30HP@480V). It provides a 24V DC coil, 1NO built-in auxiliary contacts, connection by screw clamp terminals. Compact (55mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA), Green Premium compliant (RoHS/REACh).
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Coil Technology:
- without built-in suppressor module
- Pollution Degree:
- 3
- Inrush Power In W:
- 19-19 W 20°C)
- Hold-In Power Consumption In W:
- 7.4-7.4 W 20°C
- Product Certifications:
- cULus
- Tightening Torque:
- power circuit 7 N.m screw connectors 16-25 mm² hexagonal 4 mm || power circuit 5 N.m screw connectors 2.5-16 mm² hexagonal 4 mm || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || control circuit 1.7 N.m screw clamp terminals flat Ã
- Power Dissipation Per Pole:
- 3.7 W AC-3 || 9.6 W AC-1
- Operating Time:
- 4...19 ms opening || 12...26 ms closing
- Product Or Component Type:
- contactor
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 800 A at 440 V for power circuit conforming to IEC 60947
- Height:
- 122 mm
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 100 A gG at <= 690 V coordination type 1 for power circuit || 100 A gG at <= 690 V coordination type 2 for power circuit
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V cUL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V cUL
- Operating Altitude:
- 0...6561.68 ft (0...2000 m)
- [Icw] Rated Short-Time Withstand Current:
- 400 A 40°C - 10 s for power circuit || 810 A 40°C - 1 s for power circuit || 84 A 40°C - 10 min for power circuit || 208 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
- Average Impedance:
- 1.5 mOhm - Ith 80 A 50 Hz for power circuit
- Pole Contact Composition:
- 3 NO
- Mechanical Durability:
- 5 Mcycles
- Contactor Application:
- motor control || resistive load
- Poles Description:
- 3P
- Signaling Circuit Frequency:
- 25...400 Hz
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Mercury Free:
- Yes
- [Uc] Control Circuit Voltage:
- 24 V DC
- Depth:
- 122 mm
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Range:
- Easy TeSys
- Electrical Durability:
- 0.6 Mcycles 60 A AC-1 <= 440 V || 1 Mcycles 40 A AC-3 <= 440 V
- Heat Dissipation:
- 4-5 W 50/60 Hz
- Overvoltage Category:
- III
- Ambient Air Temperature For Operation:
- -40-60°C
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Circularity Profile:
- ENVEOLI1503009EN
- Maximum Horse Power Rating:
- 3 hp at 115 V AC 50/60 Hz for 1 phase motors || 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 10 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 10 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 30 hp at 460/480 V AC 50/60 Hz for 3 phase m
- Environmental Disclosure:
- ENVPEP1503009EN
- Auxiliary Contacts Type:
- mechanically linked 1 NO IEC 60947-5-1
- Eu Rohs Directive:
- Compliant with Exemptions
- Rated Breaking Capacity:
- 800 A at 440 V for power circuit conforming to IEC 60947
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Connections - Terminals:
- power circuit: screw connection 1 2.5-25 mm² - cable stiffness: flexible without cable end || power circuit: screw connection 2 2.5-16 mm² - cable stiffness: flexible without cable end || power circuit: screw connection 1 2.5-25 mm² - cable stiffn
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 60947-4-1
- Control Circuit Type:
- DC 50/60 Hz