Schneider Electric AK5JB144 Busbar Tetra 160A Lg 452
Schneider Electric
$266.00
Linergy busbar for AC network. It applies to distribution, 12 Tap-offs and 4 conductors. The rated operational current is 160 A at 35 °C. Mounting by horizontal and vertical which using side stop AK5BT01 on mounting plates AK5PA. It provides protection for AM fuses, GF fuses and NS160H circuit breaker. IPxx B conforming to IEC 60529 and 850 °C fire resistance conforming to IEC 60695. It conforms to IEC 60439 standard. Multi standards certified (CSA, DNV, UL, LROS (Lloyds register of shipping). It conforms to RoHS.
- Number Of Conductors:
- 4
- Product Name:
- HK
- Network Type:
- AC
- Bar Length:
- 452 mm
- [Ie] Rated Operational Current:
- 160 A 35 °C
- Peak Current:
- 25 kA
- Number Of Tap-Offs:
- 18
- Mercury Free:
- Yes
- Environmental Disclosure:
- ENVPEP120206EN
- Depth:
- 82 mm
- [Ui] Rated Insulation Voltage:
- 600 V CSA || 600 V UL || 690 V IEC 60439-1
- Circularity Profile:
- N/A
- Reach Free Of Svhc:
- Yes
- Enclosure/Cubicle Width:
- 800 mm
- Warranty:
- 18 months
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Fire Resistance:
- 850 °C IEC 60695
- Eu Rohs Directive:
- Compliant
- Toxic Heavy Metal Free:
- Yes
- Width:
- 81 mm
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Net Weight:
- 0.9 kg
- Sustainable Offer Status:
- Green Premium product
- Flame Retardance:
- V0 conforming to UL 94
- Device Application:
- distribution
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Bar Width:
- 45 mm
- Product Or Component Type:
- busbar
- Ip Degree Of Protection:
- IPxx B conforming to IEC 60529
- Connections - Terminals:
- connector 2.5-70 mm² flexible with cable end || connector 2.5-70 mm² rigid
- Range:
- Linergy
- I²T On Activation:
- 10000000 A².s
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- [Ue] Rated Operational Voltage:
- 400 V off-load plugging-in and unplugging, with supply switched on)IEC 60439-1 || 480 V off-load plugging-in and unplugging, with supply switched on)CSA || 480 V off-load plugging-in and unplugging, with supply switched on)UL || 600 V plugging-in and
- Mounting Position:
- vertical using side stop AK5BT01 on mounting plates AK5PA || horizontal
- Standards:
- IEC 60439
- Protection Type:
- aM fuses In = 160 A, Isc = 100 kA, Ie = 160 A || gF fuses In = 160 A, Isc = 100 kA, Ie = 160 A || NS160H circuit breaker In = 160 A, Isc = 36 kA, Ie = 160 A || NS160H circuit breaker In = 160 A, Isc = 70 kA, Ie = 160 A
- Tightening Torque:
- 10 N.m
- Network Frequency:
- 50/60 Hz
- Rohs Exemption Information:
- Yes
- Product Certifications:
- UL || CSA || DNV || LROS (Lloyds register of shipping)
- Catalog:
- View
- Datasheet:
- View